Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.7.1.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset. Exterior window is desirable. Partitions shall have minimum STC
rating of 55.
Chaplain. Provide one; 9.8 m2 [105 sf]. Room shall be accessed from the
2-5.7.2
Chaplain's Assistant office, and the corridor. Occupants: 1, and visitors.
2-5.7.2.1 Function: Private office for Chaplain and visitors.
2-5.7.2.2 Adjacency requirements: Adjacent to Chaplain's Assistant, and corridor
2-5.7.2.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate one
desk [____] with return [____], one bookcase [___],one desk chair, and [insert furniture
requirements].
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.7.2.5 Other requirements: Provide 914 mm [3'-0"] wide doors into room; doors shall have
entry function (F81) lockset. Room shall have exterior window. Partitions shall have minimum
STC rating of 55.
Surgeon. Provide one; 9.8 m2 [105 sf]. Room shall be accessed from the
2-5.7.3
corridor/lobby. Occupants: 1, and visitors.
2-5.7.3.1 Function: Private office for brigade surgeon (doctor).
2-5.7.3.2 Adjacency requirements: Adjacent to corridor/main lobby.
2-5.7.3.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate one
desk [____] with return [____], one bookcase [___], one side chair, and one desk chair.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.7.3.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset. Room shall have exterior window. Partitions shall have minimum
STC rating of 55.
Supply Closet. Provide one; 1.9 m2 [20 sf]. Room shall be accessed from the
2-5.7.4
corridor. Occupants: none.
SOW-72