Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-5.8.6.1 Function: Storage of [identify type of items to be stored] for the brigade.
2-5.8.6.2 Adjacency requirements: Adjacent to corridor/lobby
2-5.8.6.3 Furnishings/Fixtures/Equipment: [insert shelving requirement].
2-5.8.6.4 Finishes: Floor: sealed concrete
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: suspended acoustical panel ceiling
2-5.8.6.5 Other requirements: Door shall have storeroom function (F86) lockset.
2-5.9
Battalion HQ Support Areas. Provide the following areas in each battalion HQ
building. Handicapped accessibility is not required in mechanical rooms, electrical and
communications closets. All other support spaces shall be handicap accessible.
2-5.9.1
Mechanical Room(s). Provide dedicated areas for mechanical equipment.
Mechanical rooms shall not be used for storage or other purposes. Access will be limited to
authorized personnel. Size and locate room(s) to allow equipment removal and maintenance.
Provide floor openings and vertical shaft spaces as necessary.
2-5.9.1.1 Function: Spaces for HVAC, water heating, and other plumbing and mechanical
equipment.
2-5.9.1.2 Adjacency requirements: Locate to allow efficient distribution. Mechanical rooms
shall have doors opening to the exterior.
2-5.9.1.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
2-5.9.1.4 Finishes: Floor: sealed concrete
Base: resilient cove base, or none.
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required
2-5.9.1.5 Other requirements: Doors shall have storeroom function (F86) locksets.
2-5.9.2
Electrical Room(s). Provide dedicated areas for electrical equipment. Electrical
rooms shall not be used for storage or other purposes. Access will be limited to authorized
personnel. Size and locate room(s) to allow equipment removal and maintenance.
2-5.9.2.1 Function: Spaces for electrical equipment.
2-5.9.2.2 Adjacency requirements: Locate to allow efficient distribution. Electrical rooms shall be
accessed from the exterior or from corridors.
2-5.9.2.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
2-5.9.2.4 Finishes: Floor: sealed concrete
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
SOW-76