2-5.9.2.5 Other requirements: Electrical service to buildings shall be underground. Doors
shall have storeroom function (F86) locksets.
2-5.9.3
Communication Room. Provide dedicated room(s) for communication distribution
equipment. Each room shall be dedicated to communications equipment, and shall not be
combined with mechanical or electrical rooms. Provide one main communication room;
minimum size 3048 mm [10'-0"] x 3353 mm [11'-0"]. In two-story buildings, the communication
room shall be located on the second floor. Provide additional communication rooms as needed;
all spaces having telephone or computer data outlets shall be located to allow a maximum cable
length of 90 m [295 feet] between outlet and communication room. Minimum dimensions of
secondary communication rooms shall be 2134 mm [7;-0"] x 3048 mm [10'-0"]. Provide floor
openings and vertical shaft spaces as necessary. Rooms shall be accessed from corridors.
Access will be limited to authorized personnel.
2-5.9.3.1 Function: Distribution areas for telephone, data network, and cable television.
2-5.9.3.2 Adjacency requirements: Adjacent to corridor. Locate to allow efficient distribution.
2-5.9.3.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: painted gypsum wallboard, painted veneer plaster, or suspended acoustical panel ceiling
2-5.9.3.5 Other requirements: Provide minimum 914 mm [3'-0"] wide door with storeroom
function (F86) lockset.