Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
appropriately].
5-4.3
Roofs. Sloped roofs with a minimum pitch of [__] : 12 shall be used on all buildings.
Roofing material and color shall comply with IDG. Roofing system shall have Underwriters
Laboratory (UL) Class A rating for fire resistance, UL 90 wind resistance rating, and Factory
5-4.3.1
Metal Roofing. Provide manufacturers 20-year finish warranty.
5-4.3.2
Asphalt Shingle Roofing. Provide minimum 30-year shingles; provide minimum
30# felt underlayment. Provide self-adhering rubberized ice and water shield underlayment at
all valleys, and roof perimeter [review requirement in regard to local climate].
5-4.4
Trim and Flashing. Materials and colors shall comply with IDG. [Review the IDG to
make sure that trim and flashing materials and colors are sufficiently covered.] Gutters,
downspouts, and fascias shall be prefinished metal; comply with SMACNA Architectural Sheet
Metal Manual; provide 20 year manufacturers finish warranty.
5-4.5
Miscellaneous Exterior Elements. Comply with IDG. [review the IDG to make sure
that trim and minor elements are sufficiently covered. It is advisable to prohibit any use of
exterior wood with painted finish; require prefinished metal trim. If not stated in IDG, require
exterior metal railings to be prefinished aluminum, or if acceptable to installation facilities
engineer (DPW), allow the more economical option of using field-painted (and adequately pre-
treated) galvanized steel railings. Coordinate with user to include requirements for any building-
beacons, etc.].
5-4.6
Signage. Comply with IDG. [Coordinate with installation facilities engineer (DPW);
provide criteria for quantity, type, size and location of building identification signs. Note whether
5-4.7
Exterior Doors and Frames.
5-4.7.1
Main Entrance Doors. Doors opening to building corridors or lobbies shall be
aluminum storefront doors and frames with Architectural Class I anodic finish or AAMA 2605
organic coating finish. Color shall comply with IDG. Doors shall be minimum 45 mm [1-3/4"]
thick. Fully glazed stile and rail doors shall be medium or wide stile. Provide aluminum
storefront systems that comply with wind load requirements of applicable codes. Framing
systems shall have thermal-break design.
5-4.7.2
Exterior Non-entrance Doors. Exterior doors and frames opening to spaces other
than corridors or lobbies shall be hollow metal; comply with ANSI A250.8/SDI 100. Doors shall
be Level 3, physical performance Level A, Model 2; insulated; top edge closed flush. Frames
shall be Level 3, 14 gauge, with continuously welded corners and seamless face joints. Doors
and frames shall be constructed of hot dipped zinc coated steel sheet, complying with ASTM
A653, Commercial Steel, Type B, minimum A40 coating weight; factory primed. Anchors and
accessories shall be zinc coated. Frames in masonry shall have bituminous back-coating,
plaster guards, and shall be grouted solid. Fire-rated openings shall comply with NFPA 80, and
the requirements of the labeling authority.
5-4.7.3
Exterior Door Finish Hardware.
SOW-108