Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
5-4.7.3.1 Hinges. ANSI/BHMA A156.1; template, full mortise, heavy duty, ball bearing,
minimum size 4 " x 4 ", non-ferrous base metal, non-removable pins.
5-4.7.3.2 Locksets on Living Unit Entry Doors. ANSI/BHMA A156.13; mortise lockset with
removable core; non-ferrous base metal.
5-4.7.3.3 Locksets on Exterior Hollow Metal Doors. ANSI/BHMA A156.2; series 4000,
Grade 1, non-ferrous base metal, removable core.
5-4.7.3.4 Exit (Panic) Devices. ANSI/BHMA 156.3; heavy-duty touch-pad type, through-
bolted mounting. Listed and labeled for panic protection based on UL 305.
5-4.7.3.5 Closers. ANSI/BHMA A156.4; series C02000, Grade 1, hydraulic, factory-sized,
adjustable to meet field conditions. Provide for all exterior doors, all entry doors to living units,
all doors opening to corridors and as required by codes. At exterior doors to lobbies, corridors,
mechanical rooms, janitors closets, and COF supply areas provide overhead holders or closers
with hold-open capability.
5-4.7.3.6 Auxiliary Hardware. ANSI/BHMA A156.16. Provide wall or floor stops for all
exterior doors that do not have overhead holder/stops. Provide other hardware as necessary
for a complete installation.
5-4.7.3.7 Thresholds. ANSI/BHMA A156.21; non-ferrous metal. Provide at all exterior doors.
5-4.7.3.8 Weatherstripping. ANSI/BHMA A156.22. Provide at all exterior doors.
5-4.7.3.9 Kick Plates. ANSI/BHMA A156.6; non-ferrous metal. Provide at all doors with
closers.
5-4.8
Exterior Windows. Provide aluminum windows complying with American
Architectural Manufacturers Association AAMA/NWWDA 101 / I.S. 2. Minimum performance
class shall be Heavy Commercial (HC). Minimum wind load, and resulting design pressure and
performance grade shall be determined in accordance with the International Building Code
(IBC). Provide windows with insulating glass and thermal break necessary to achieve a
cold climates]. Finish shall be Architectural Class I anodic coating or AAMA 2605 organic
coating [Edit to allow anodic coating if clear or bronze anodized color is acceptable]. All
sleeping rooms shall have operable windows complying with egress requirements of applicable
codes. Operable windows shall have locks; provide fiberglass or aluminum insect screens
removable from the inside.
5-4.8.1
Exterior Glass and Glazing. To comply with force protection minimum standards:
Single glazing and the inner pane of insulated glass assemblies in exterior windows and doors
shall be minimum 6 mm (1/4-inch) annealed laminated glass.
5-4.9
Thermal Insulation. Provide exterior wall, floor, and roof/ceiling assemblies with
thermal transmittance (U-values) required to comply with the proposed energy calculations for
the facilities. Insulation shall not be installed directly on top of suspended acoustical panel
ceilings.
SOW-109