26 November 2001
material.
5-5.7.2
Bathroom Vanity in Living Units. Provide manufactured unitized kitchen, or
provide architectural cabinets complying with AWI Quality Standards, Section 400, Custom
Grade cabinets with high-pressure decorative laminate finish, meeting NEMA LD3 standards.
Horizontal laminate :nominal .048" thick; vertical laminate nominal .028" thick. Door and drawer
edges shall be heavy duty 3 mm extruded polyvinyl chloride with self-locking serrated tongue.
Vanity countertop shall be post-formed high pressure decorative laminate with waterfall front
edge and integral coved backsplash, or solid surfacing material, or cast-filled acrylic with
integral lavatory bowl.
5-5.7.3
UEPH Building CQ Station Reception Desk. Provide architectural casework
complying with AWI Quality Standards, Section 400, Custom Grade cabinets with high pressure
decorative laminate finish meeting NEMA LD3 standards. Horizontal laminate: nominal .048"
thick; vertical laminate: nominal .028" thick. Door and drawer edges shall be heavy duty 3 mm
extruded polyvinyl chloride with self-locking serrated tongue. Worksurfaces and counter shall
be high pressure decorative laminate, or solid surfacing material.
5-5.7.4
Vanity at Public Toilets. Provide architectural casework complying with AWI
Section 400, Custom Grade cabinets with high pressure decorative laminate finish meeting
NEMA LD3 standards. Horizontal laminate: :nominal .050" thick; vertical laminate: nominal
.028" thick. Provide enclosed wall-hung vanity cabinet with countertop, or wall-hung countertop
with apron. Exposed piping at accessible lavatories shall be insulated in conformance with
ADA/UFAS. Countertop shall be post-formed high pressure decorative laminate with waterfall
front edge and integral coved backsplash, or solid surfacing material.
5-5.7.5
Other casework. Provide architectural casework complying with AWI Section 400,
Custom Grade cabinets with high pressure decorative laminate finish meeting NEMA LD3
standards. Horizontal laminate: nominal .050" thick; vertical laminate: nominal .028" thick. Door
and drawer edges shall be heavy duty 3 mm extruded polyvinyl chloride with self-locking
serrated tongue. Worksurfaces and counter shall be high pressure decorative laminate, or solid
surfacing material.
5-5.8
Window Treatments. Provide horizontal aluminum mini-blinds at all exterior
windows, except windows and storefront in corridors and lobbies. Blinds shall have one-inch
wide x .008-inch thick slats with anti-static, anti-microbial polyester baked enamel finish.
Provide heavy duty 1" x 1-1/2" steel headrail, and tubular steel bottom rail finished to match
slats.
5-5.9
Interior Signage. Comply with requirements of ADAAG and UFAS. Provide interior
room identification signage for the following spaces: Public toilets, [Coordinate with user and
installation facilities engineer (DPW). Identify all rooms which require room identification
signage; coordinate with the installation interior signage standard, if one exists].
5-5.10
Elevators.
The offeror shall provide the services of an
elevator inspector employed
by an independent testing company to inspect the elevator, witness the final testing, and certify
elevator. The inspector shall meet all qualification requirements of ASME QEI-1 and shall be
certified in accordance with ASME QEI-1. The offeror shall provide an elevator certificate
signed by the inspector for each elevator. The certificate shall be provided to the Contracting
Officer within 30 days of the completion of testing.