TABLE 4-9. NAVY TEEN/STAFF/VISITOR TOILETS
Navy provides multiple (as needed) unisex toilets for use by Teens, Staff and visitors.
Description/
Quantity of toilets is based on the applicable code for the calculated occupancy. The
Usage
other Services do not use unisex toilets. See Table 3-1 for Service-specific toilet
requirements.
2.44 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. Epoxy or enamel painted, moisture-resistant gypsum wallboard with a ceramic
tile wainscot. Provide full-height ceramic tile on wet walls; consider full-height ceramic
tile on all walls.
Floor. Ceramic tile.
Ceiling. Painted, moisture-resistant gypsum board.
One wall-hung water closet and lavatory. Provide a floor drain.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum. Ventilate to the exterior per code.
HVAC
Provide system per paragraph 3-5.3.
Fire Protection
Provide outlets per code.
Power
540 lux (50 fc).
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. Lockable door.
Casework
Solid-surface countertop supported at both ends with either underhung or integral sink.
A wall-hung lavatory is also acceptable.
Wall-hung water closets.
Toilet accessories: toilet paper dispensers, paper towel dispenser with integrated
Furnishings
trash receptacle, robe hooks, grab bars, and soap dispensers.
Fixtures &
Equipment
Mirror.
(FF&E)
This room must be ADA-compliant.
Special
Requirements
For use during project execution by the appropriate Service agency
Staff.
Occupancy
Patrons/Youth.
Min. net m2 (ft2)
55