4-1.8
All equipment indicated for spaces below is part of the design and
construction, unless noted as provided by Government or Tenants.
4-2
tRAInInG CenteR BUILDInG
4-2.1
Full-time Offices
4-2.1.1 Full-time offices are used by permanent USAR staff for the daily
administration tasks associated with the unit s mission and the operation of the facilities.
The full-time staff typically works 8-hour days from Monday to Friday, and they are the
major building Tenants during the week. Design of these spaces will be similar to a
typical business office.
4-2.1.2 Full-time offices may be designed for a single occupant or for multiple
occupants, based on Tenant requirements and functional efficiency. In some cases, the
Design Agency may wish to recommend combining some full-time offices for reasons of
design efficiency or flexibility.
4-2.1.3 \ Provide one each single quad power receptacle at each desk location to
accommodate potential for a variety of equipment that may be utilized. On the "U"
configured desk units, place the single quad power receptacle at the bridge location and
on the "L" configured desk units, place the single quad power receptacle at the return
location./2/ Avoid room arrangements that have the occupants back tot he door.
4-2.1.4 \ General Officer and staff suite, O6 Commanding Officers and O6
Commanding Officer s Command Sergeant Major offices shall be distinguished from
typical private offices with the use of traditional wood furniture./2/
4-2.1.5
Space Design Information
General/Code
Size 120 sf (11 sq m) each typical; larger for higher ranks
Occupancy business
Occupancy count varies; 1 person per workstation
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8 ft - 8 in (2600 mm)
Floor carpet \tle/2/; VCT as an alternative
Base rubber
Walls painted gypsum board
Ceiling suspended acoustical ceiling tile (ACT)
Trim coat rack mounted on the wall behind the door
Lockset office
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
Cooling, occupied 7825 degrees F (25 C); maintained ambient
Ventilation comply with ASHRAE 62.1