UFC 4-214-02, 24 Jul 03
Ceiling: prefinished metal liner panels on underside of roof purlins; exposed structure shall be
painted. Ceiling/roof height shall allow bridge crane hook cradle height of [6000 mm] [for 7
metric ton crane] [7600 mm] [for 32 metric ton crane. [Edit as applicable; if the 32 metric ton
crane is required on one wing of repair bays, and the 7 metric ton crane on the other wing of
bays, the building height and heated volume may be reduced by allowing a lower roof height on
the bays with the smaller crane. Visual effect of differing roof heights should also be
considered].
2-2.1.2.5 Other requirements: Electrical receptacles in bay area shall be minimum 610 mm
above floor (refer to Chapter 9). Provide continuous 150 mm wide trench drains with continuous
grating along full width of bays at exterior doors; locate drains approximately 1000 mm from
inside face of exterior walls. Provide 300 mm diameter x 1400 mm high, concrete-filled,
schedule 80 galvanized steel, pipe bollards inside the bay at each vehicle door jamb (refer to
Chapter 3 for exterior pipe bollards). Provide [insert number] grounding points on each bay
floor.
SOW-10