Figure 2.3 Maintenance Pit Details (Not to Scale)
2-2.1.3
Circulation Bays. Provide one circulation bay per three repair and scheduled
maintenance bays; net area shall be 47 m2 each. Bay size shall be 2400 mm wide (column
centerline to column centerline) x 19 600 mm deep (exterior face of column to exterior face of
column). Provide minimum 915 mm [3'-0"] wide x 2134 mm [7'-0"] high personnel doors at front
and rear exterior walls to allow egress from bay areas. Walls or partitions between circulation
bay and adjacent core areas shall be concrete masonry or concrete.
2-2.1.3.1 Function: pedestrian circulation into and out of the bay areas
2-2.1.3.2 Adjacency requirements: Adjacent to repair bays, and/or scheduled maintenance
bay(s). At each wing of repair bays, one circulation bay shall be adjacent to the tool room, tool
box storage and PLL areas of the core. Adjacent to hardstand areas surrounding the building
aisles.
2-2.1.3.3 Furnishings/Fixtures/Equipment: Provide 1219 mm high x 2438 mm wide tackboard
for `safety board') mounted on wall between tool room and circulation bay. Provide 400 mm
diameter battery operated wall clock mounted above tackboard. Provide one emergency eye
wash at each Circulation Bay that is adjacent to a core area; locate eye wash adjacent to the
wall separating the Circulation Bay from the core. [Insert additional requirements].
2-2.1.3.4