Project Name
Project Number
TEMF
Statement of Work
UFC 4-214-02, 24 Jul 03
(refer to Chapter 9). Provide continuous solid cover at trench drains within shop. Provide 300
mm diameter x 1400 mm high, concrete-filled, schedule 80 galvanized steel, pipe bollards inside
the shop at each vehicle door jamb (refer to Chapter 3 for exterior pipe bollards). Provide
emergency eye wash. Provide minimum of [insert number] grounding points on floor. Provide
2-2.1.5
Generator Shop. One-half of one repair bay shall be dedicated to generator shop
area; net area is included in provided repair bay area [Delete this paragraph if user organization
is not authorized generator shop space]. Provide acoustical concrete masonry unit partitions to
define perimeter of shop; locate partitions on column centerlines and at bay centerline.
Masonry thickness shall be as required to comply with applicable codes, but not less than 200
mm thick. Masonry partitions shall terminate 200 mm above ceiling, and shall be braced to
building structure; bracing shall not project into the overhead (crane space) of the surrounding
bay areas. Provide acoustical metal panel ceiling at minimum [___] above floor slab in the half
bay dedicated as a generator shop. Ceiling installation shall not impede operation of the
overhead bridge crane. Exterior wall of shop shall be the repair bay exterior wall, including the
7400 mm wide x 4300 mm high overhead door at exterior wall (refer to repair bay criteria).
Provide personnel egress doors as required by applicable codes. One personnel access door
shall open to adjacent circulation bay.
2-2.1.5.1 Function: repair of power generation equipment. [verify function with user].
2-2.1.5.2 Adjacency requirements: Adjacent to circulation bay, repair bays and/or scheduled
maintenance bay. Adjacent to hardstand vehicle access aisles.
2-2.1.5.3 Furnishings/Fixtures/Equipment: Provide minimum of 2 compressed air outlets in the
shop. Provide electrical power to accommodate user furnished equipment [Include power, and
other criteria for user provided equipment].
Floor: epoxy coating on concrete
Base: none
Walls: exposed acoustical concrete masonry units. Exposed structure shall be painted.
Ceiling: Prefinished acoustical metal panel ceiling. [Government will consider alternate
materials for ceiling construction providing an equivalent barrier. The responsibility to prove
equivalency with a prefinished acoustical metal panel ceiling shall rest with the offeror at
proposal stage.]
2-2.1.5.5 Other requirements: Electrical receptacles shall be minimum 610 mm above floor
(refer to Chapter 9). Provide continuous solid cover at trench drains within shop. Provide 300
mm diameter x 1400 mm high, concrete-filled, schedule 80 galvanized steel, pipe bollards inside
the shop at each vehicle door jamb (refer to Chapter 3 for exterior pipe bollards). Provide
emergency eye wash. Provide minimum of [insert number] grounding points on floor.
2-2.1.6
Paint Bay. [Net area for paint bay is included in provided repair bay area. Paint bay
space is typically authorized only for certain DOL, DPW and general support organizations.
Delete this paragraph if user organization is not authorized paint bay space. Coordinate criteria
for paint booth, filters, exhaust system, breathing air system, paint mixing, stoage and
dispensing systems, etc. with user requirements. In the SOW include specific information
regarding user requirements, and include performance criteria for design of paint booth and
related equipment. Research environmental impact on the project].
SOW-14