Project Name
Project No. ___________
UFC 4-721-11.1, UEPH Complexes, 26 Nov 01
11.3.6.3 The final structural drawings shall contain the following information as a set of general notes:
The allowable soil bearing value.
The design stresses of structural materials used.
The design live loads used in the design of various portions of the structures.
The design wind speed.
The seismic zone and the "K", "C", "I" and "Z" values used in design.
11.3.6.4 All structural drawings and calculations shall be checked and stamped by the designer of
record (a registered Professional Engineer).
[11.3.7 Fire Suppression System: Provide a file of the input data used in the computer program to
design the fire suppression system as well as the output data.]
1
1.3.8 Specific Mechanical and Plumbing Requirements:
11.3.8.1 Required Plans, Diagrams, Schedules and Details on Unit Mechanical Drawings:
11.3.8.1.1. Mechanical Floor Plan: The floor plans shall show all principle architectural features of the
building which will affect the mechanical design. The floor plans shall also show the following:
Room designations.
Mechanical legend and applicable notes.
Location of all ductwork or piping (double line ductwork required).
Location and capacity of all terminal units (i.e., registers, diffusers, grilles, hydronic baseboards).
Exhaust fan and range hood location.
Size of all ductwork and piping.
Thermostat location.
Location of heating/cooling plant (i.e., boiler, chiller, cooling tower, etc).
Location of all air handling equipment.
Return air paths (i.e., undercut doors, transfer grilles).
Flue piping size and location.
Piping diagram for forced hot water system (if used).
Fuel supply and return piping
11.3.8.1.2. Equipment Schedule: Complete equipment Schedules shall be provided. Schedule shall
also include:
Capacity
Electrical characteristics
Efficiency (if applicable)
Manufacturer's name
Optional features to be provided
Physical size
11.3.8.1.3 Details: Construction details, sections, elevations, etc., shall be provided where required for
clarification of methods and materials of design. Roof and exterior wall penetrations shall be detailed
on the drawings.
11.3.8.2 Plumbing Floor Plan: The floor plan shall show all principal architectural features of the
building which will affect the plumbing design. Separate plumbing plans will not be required if
sufficient information can be shown on the mechanical plans to meet the requirements shown above.
The floor plan shall also show the following:
Room designations.
S
ection 01012 - Page 15