UFC 4-171-05
1 January 2005
with change 25 October 2006
electrical
Lighting 50 fc; dual-level switching; provide additional controls at marker board
\ - Provide receptacle for ceiling mounted overhead projector /2/
Voice/data two voice/data duplex receptacles \ at the instructor location
- one data receptacle at each student location
- Two conduits from the overhead projector location, one to the instructors
location the other to center of the wall at the rear of the classroom (if rear
of classroom is a moveable partition locate outlet box in wall at either end
of the partition /2/
||content||
\ Furniture
\ Folding tables with t-legs /2/
Sled-based stacking chairs without arms, with upholstered seat and back
Full height lectern; pedestal type with shelf underneath (table-top lectern
optonal) \/2/
equipment
Powered projection screen
Marker board with two inch (2") map rail; multiple marker boards provided where
appropriate
Two inch (2") map rail continuous around the perimeter of room.
Map rails to include end stops and hanger clips
special features or considerations
Consider incandescent downlights with dimmer to 15 fc for room darkening
Provide room-darkening shades for windows
Verify if Tenants require CATV or permanent mount for LCD projection (TV and
projector would be Tenant provided)
Provide sufficient data jacks for computer training, with wire management and
appropriate lighting/1/
\ Provide blocking in ceiling for an overhead projector /2/
4-2.14
Library Reading Room
4-2.14.1 The library reading room, or library, provides the Tenants a place to review
training publications and other reading material. It is occasionally used as a meeting or
conference room.
4-2.14.2 Library materials are stored in the library storage room storage room.
4-2.14.3 Space Design Information
General/Code
Size varies
Occupancy business, unless 4.2.12.5 above governs
Occupancy count 1 person per 20 sf (1.9 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8 ft - 8 in (2600 mm)
101