UFC 4-171-05
1 January 2005
with change 25 October 2006
Ceiling height 8 ft - 8 in (2600 mm)
Figure 4-17
Floor VCT
Library Storage
Base rubber
Walls painted gypsum board
Ceiling suspended acoustical ceiling tile (ACT)
Trim none
Lockset storeroom
Mechanical
Heating, occupied 68 degrees F (20 C); maintained
- 55 degrees F (13 C)
Coolng - none
Ventilation comply with ASHRAE 62.1
electrical
Lighting 30 fc
Voice/data wall phone
Furniture
Bookcases and/or storage cabinets
equipment
Open shelving
special features or considerations
4-2.16
Learning Center
4-2.16.1 This space is used as a computer training space. It can be used for individual
testing or group instruction.
Figure 4-18
4-2.16.2 Space Design Information
Learning Center
General/Code
Size varies
Occupancy business, unless 4.2.12.5 above
governs
Occupancy count 1 person per 20 sf (1.9 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8ft - 8 iin (2600 mm)
Floor carpet \tle/2/; VCT as an alternative
Base rubber
Walls painted gypsum board
Ceiling suspended acoustical ceiling tile (ACT)
Trim \ none /2/
Lockset classroom
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
Cooling, occupied 78 degrees F (25 C); maintained ambient
Ventilation comply with ASHRAE 62.1
103