UFC 4-171-05
1 January 2005
with change 25 October 2006
electrical
Lighting 50 fc
\ - Provide receptacle for ceiling mounted overhead projector /2/
Voice/data telephone and data outlets
\ - Conduits from the overhead projector location to the instructors
location/2/
||content||
\ Furniture
Tables with c-legs on castors, wire management basket, sling type CPU holder,
Table to be 30 in (762 mm) deep and long enough to accommodate 2
computers with three-ring binder space between
Mid-back upholstered task chairs with adjustable arms
Height adjustable upholstered stool with arms
Combination lectern to hold computer, monitor and keyboard connected to a
projection screen
Lockable storage cabinet with shelves
equipment
Marker board with 2" map rail; map rail to include end stops and hangerclips
Powered projection screen wired to instructor s lectern to allow instructor s
computer screen to be projected
special features or considerations
Power outlets and data outlets should be provided along the wall at each table
location ease of access
If the room is lined with room dividers instead of hard walls, floor outlets may be
an opton/1/
\ Provide blocking in ceiling for an overhead projector /2/
4-2.17
Training Aids Storage
4-2.17.1 This space is for the storage of teaching aids (including A/V equipment),
manuals, publications, and models. The designer should verify the types of materials to
be stored, and design the space accordingly.
Figure 4-19
Training Aids
4-2.17.2 Space Design Information
Storage
General/Code
Size 10% times total classroom area authorization
Occupancy business
Occupancy count not occupied; typically 1 person per
300 sf
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8 ft - 8 in (2600 mm)
Floor VCT
Base rubber
Walls painted gypsum board