UFC 4-171-05
1 January 2005
with change 25 October 2006
(8 ft by 12ft - 2n) /2/ cages constructed of woven welded wire fabric. See Section 3-5.6
for additional information on cages and shelving. Aisles and vestibules between the
secured areas should allow for efficient circulation and movement of stored equipment.
Circulation space is not included within the total area authorization.
4-2.20.3 Space Design Information
Figure 4-21
Unit Storage with
General/Code
Supply Office
Size varies
Occupancy storage
Occupancy count not occupied; typically 1 person per
300 sf (27.9 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 10 ft (3050 mm) minimum
Floor sealed concrete
Base none
Walls painted CMU; painted gypsum board as an
alternative
Ceiling none; paint structure
Trim none
Lockset classroom; padlocks at cages
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
Cooling economizer only
Ventilation one air change per hour
electrical
Lighting 30 fc; motion sensors for aisles
Receptacles convenience duplex in each cage; convenience duplexes along
aisles
Voice/data none
Furniture - none
equipment - none
special features or considerations
Ordinary hazard sprinklers
Lights should be located at cage ceilings, as well as in aisles, to provide
sufficient light for cages and allow for ease of bulb replacement
Provide padlocks for all cage door hasps
If some portions of unit storage have gypsum board walls, consider a plywood
wainscot
108