UFC 4-171-05
1 January 2005
with change 25 October 2006
attempted entry.
4-2.19.4 Air vents, ducts and similar openings that breach the room envelope must be
secured to prevent penetration; if greater than 96 sq in (2,000 sq mm), provide
hardened steel bar grates or IDS supervision. All openings must be baffled to limit
audio or acoustical transmission to non-COMSEC spaces.
4-2.19.5 Space Design Information
General/Code
Size varies
Occupancy business
Occupancy count not occupied, typically 1 person per 300 sf
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8 ft - 8 in (2600 mm)
Floor VCT
Base rubber
Walls painted gypsum board
Ceiling painted gypsum board
Trim none
Lockset storeroom
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
Cooling none
Ventilation incidental
electrical
Lighting 30 fc
Voice/data wall phone
Furniture
Verify with Tenants
equipment
Any safe(s) will be provided by with the Tenants
Open shelving
special features or considerations
Ordinary hazard sprinklers
Though not a requirement, Tenants normally prefer no windows in this space
4-2.20
Unit/Individual Storage
4-2.20.1 This space permits storage and inventory management of organizational
equipment, such as clothing, tents, radios, tool sets, etc., in a separate and secure area.
The issue and return of organizational equipment is also conducted here, or in the
staging area.
4-2.20.2 The unit storage space is typically subdivided into 2400 mm by \ 3650 mm
107