UFC 4-171-05
1 January 2005
with change 25 October 2006
Furniture
equipment
special features or considerations
Overhead	door	to	the	exterior,	typically	10	ft	by	10	ft	(3	m	by	3	m)
\	Provide	6-inch	diameter	concrete	filled	with	a	concrete	dome	top,	heavy-
weight	steel	protective	bollards	inside	and	outside	of	overhead	door	jams	
/2/
If	site	conditions	allow,	consider	a	raised	or	depressed	loading	dock	at	the	
overhead	door
Ordinary	hazard	sprinklers
4-2.22
Supply	Office
4-2.22.1 These	offices	are	used	by	the	supply	officers	for	administration	and	training	
purposes.	They	should	be	located	to	have	a	view	of	the	unit	storage	and	staging	areas,	
possibly	through	a	window,	sidelight	or	door	light,	since	they	have	air	conditioning	and	
the	spaces	around	them	do	not.	An	exterior	window	overlooking	the	service	drive	to	the	
staging	area,	and	any	vehicle	barrier,	are	also	desirable.
4-2.22.2 There	is	typically	a	GFGI	safe	in	at	least	one	supply	office;	provide	a	floor	
anchor,	similar	to	that	in	the	arms	vault	at	the	appropriate	office(s).
4-2.22.3 Space	Design	Information
General/Code
Size		120	sf	(11	sq	m)	each	typical
Occupancy		business
Occupancy	count		1	person	per	single	office;	shared	offices	2-10
Architectural/Interiors
Minimum	STC	rating		40
Ceiling	height		8	ft	-	8	in	(2600	mm)
Floor		VCT
Base		rubber
Walls		painted	gypsum	board;	painted	CMU	as	an	alternative
Ceiling		suspended	acoustical	ceiling	tile	(ACT)
Trim		none
Lockset		office
Mechanical
Heating,	occupied		68	degrees	F	(20	C);	maintained		55	degrees	F	(13	C) 
Cooling,	occupied		78	degrees	F	(25	C);	maintained		ambient
Ventilation		comply	with	ASHRAE	62
electrical
Lighting		50	fc
Voice/data		two	telephone/data	duplexes	per	workstation
Furniture
Similar	to	full-time	offices	above
110