UFC 4-171-05
1 January 2005
with change 25 October 2006
Furniture
Exercise	(rubber	mats)	for	comfort	at	firing	area	and	to	cover	cables/air	lines	on	
floor	connecting	targets	and	equipment.
Control	Room
Two	folding	tables
Two	desk	chairs
Secure	Storage	Room		two		42"	shelves,	24	inches	deep	6	foot	tall
equipment
Simulator	Room
	
60"	x	60"	Powered	projection	screen	centered	on	wall	mounted	below	
ceiling	in	front	of	display	board	wall.
special features or considerations
Noise		maximum	107	decibels
	
-	Locate	Weapons	Simulator	space	away	from	offices.
Provide	room-darkening	shades	for	any	windows
Verify	equipment	power	or	data	needs	with	Tenants
Quiet	air	distribution	/2/
4-2.28
Photo	Lab
4-2.28.1 The	photo	lab	provides	space	for	photography	developing	and	processing	for	
both	operations	and	training.
4-2.28.2 A	rotary	darkroom	door	is	required,	adequate	ventilation	for	darkroom		
chemicals,	and	no	return	air	duct.
Figure 4-26
4-2.28.3 Space	Design	Information
Photo Lab
General/Code
Size		250	sf	(23.3	sq	m)
Occupancy		business
Occupancy	count		1	person	per	100	sf	(9.3	sq	m)
Architectural/Interiors
Minimum	STC	rating		40
Ceiling	height		8	ft	-	8	in	(2600	mm)
Floor		VCT
Base		rubber
Walls		painted	gypsum	board;	painted	CMU	as	an	alternative
Ceiling		suspended	acoustical	ceiling	tile	(ACT)
Trim		none
Lockset		office;	rotary	door	from	door	supplier
Mechanical
Heating,	occupied		68	degrees	F	(20	C);	maintained		55	degrees	F	(13	C) 
Cooling,	occupied		78	degrees	F	(25	C);	maintained		ambient
Ventilation		comply	with	ASHRAE	62.1
electrical
Lighting		100W	darkroom	lights	with	15W	safelight
115