UFC 4-171-05
1 January 2005
with change 25 October 2006
Receptacles convenience duplex receptacles and GFCI at wet areas
Voice/data wall phone
Furniture
Adjustable stool with back
equipment
special features or considerations
Design exhaust for chemicals to be used
Consider undercounter neutralizing basin with stainless steel sink
4-2.29
4-2.30
Medical Section
4-2.30.1 Units with medical sections assigned to them will be authorized a 400 sf
(37.2 sq m) space to be used for training and storage. The designers should coordinate
layout and furnishing for the space with the Tenants.
4-2.30.2 Space Design Information: This area may house functions similar to office,
unit common, or physical exam spaces; see space design information for those
functions as appropriate.
4-2.31
4-2.32
4-2.33
Soils Testing Lab
4-2.33.1 The space is authorized for units with soils testing functions, and should be
located near an exterior door to minimize tracking of dirt by field personnel.
4-2.33.2 Space Design Information
General/Code
Size 150 sf (13.9 sq m)
Occupancy business
Occupancy count 1 person per 100 sf (9.3 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height 8 ft - 8 in (2600 mm)
Floor VCT
Base rubber
Walls painted gypsum board
Ceiling suspended acoustical ceiling tile (ACT)
Trim none
Lockset office
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
116