Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
molded to countertop. Provide chrome-plated washerless faucet with pop-up drain (refer to
Chapter 8). Countertop shall be minimum 914mm [3'-0"] wide cast-filled acrylic, acrylic solid
surfacing material, or plastic laminate with integrally molded, 102mm high coved backsplash.
Provide 102mm high side splash at side walls. Provide plastic laminate surfaced vanity base
cabinet with hinged door(s) and minimum two 229mm [9"] wide drawers. Provide 6mm [1/4"]
thick x minimum 1067mm [3'-6"] high mirror glass, full width of vanity countertop, with wall
mounted vanity light fixture above mirror (refer to Chapter 9). Provide one recessed medicine
cabinet, one soap holder, one toothbrush/tumbler holder. Provide floor mounted toilet with full
seat and seat cover (lid). Provide bathtub, chrome-plated brass showerhead, and anti-scald
single-handle mixing valve (refer to Chapter 8). Provide two minimum 610mm [2'-0"] long towel
bars mounted on walls outside tub/shower enclosure, one wall mounted soap holder in the
tub/shower, and one door mounted robe hook with two hooks. Provide wall mounted retractable
clothesline across tub/shower. Provide mildew-resistant vinyl shower curtain with stainless
steel curtain hooks and chrome-plated brass shower curtain rod. Provide single roll toilet tissue
dispenser.
Floor: ceramic tile
Base: ceramic tile sanitary cove base
Walls: painted water-resistant gypsum wallboard or painted veneer plaster, or ceramic tile, or
ceramic tile wainscot. Walls around shower/tub enclosure shall be full height ceramic tile, or
material with equivalent scratch-resistance, water-resistance, and durability.
Ceiling: painted exterior gypsum soffit board, or painted veneer plaster, painted Portland cement
plaster, or painted underside of precast concrete structural floor planks.
2-2.2.4.5 Other requirements: HVAC system shall exhaust bathroom air; refer to Chapter 10.
Door shall have privacy function (F76) lockset.
2-2.2.5
Module Mechanical Area. Mechanical units may be located above ceilings, or in
separate mechanical closets; or through-wall packaged units may be used. Refer to Chapter
10. If mechanical closet is provided, the following requirements will apply:
2-2.2.5.1 Function: Houses HVAC unit for the module. Room shall not be used for storage or
any purpose not related to the mechanical system. Access will be limited to maintenance
personnel.
2-2.2.5.2 Adjacency requirements: Adjacent to and accessible only from exterior or public
corridor or breezeway.
2-2.2.5.3
Furnishings/Fixtures/Equipment: Provide mechanical system. Refer to Chapter 10.
Floor: sealed concrete
Base: none required
Walls: painted gypsum wallboard, painted veneer plaster, or painted concrete masonry units.
Ceiling: painted gypsum wallboard, or painted veneer plaster, or painted underside of precast
concrete structural floor planks
2-2.2.5.5 Other requirements: Provide swinging door sized to allow maintenance and removal
of mechanical unit(s). Door shall have storeroom function (F86) lockset. Room construction
shall comply with fire and smoke separation requirements of applicable codes.
SOW-11