Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
Base: resilient cove base
Walls: Wire mesh partitions will separate Unit Storage area from Equipment Maintenance and
adjacent storage areas within the COF. Provide painted impact resistant gypsum wallboard, or
painted concrete masonry units at exterior walls and walls separating Unit Storage from
adjacent COFs.
Ceiling: painted exposed structure, or wire mesh.
2-3.2.3.5 Other requirements: Provide a pair of 914 mm wide hollow metal doors opening onto
the paved service yard; doors shall have hold open devices and entry function (F82) locksets
with auxiliary deadlocks (thumb turn inside, keyed cylinder outside), or function F08 exit devices
(if exit devices are required by code). Provide 914 mm [3'-0"] wide swinging door with keyed
cylinder lock in wire mesh partition at Equipment Storage. Provide wire mesh ceiling or extend
wire mesh partitions to underside of structure above.
General Storage. Provide one area. Minimum area: Large company 33 m2 [355 sf];
2-3.2.4
Medium company 26 m2 [280 sf]; Small company 14.9 m2 [160 sf]. Provide access from
Equipment Maintenance Area.
2-3.2.4.1 Function: Storage of [
]
2-3.2.4.2 Adjacency requirements: Adjacent to Equipment Maintenance Area.
2-3.2.4.3 Furnishings/Fixtures/Equipment: [add requirements for shelving].
Floor: sealed concrete
Base: resilient cove base
Walls: Wire mesh partitions will separate General Storage area from Equipment Maintenance
and adjacent storage areas within the COF. Provide painted impact resistant gypsum wallboard,
or painted concrete masonry units at exterior walls and walls separating General Storage from
adjacent COFs.
Ceiling: painted exposed structure, or wire mesh.
2-3.2.4.5 Other requirements: Provide 914 mm [3'-0"] wide swinging door with keyed cylinder
lock in wire mesh partition at Equipment Storage. Provide wire mesh ceiling or extend wire
mesh partitions to underside of structure above.
2-3.2.5
Nuclear, Biological and Chemical Equipment (NBC) Storage.
Provide one area.
Minimum area: Large company 15.8 m2 [170 sf]; Medium company 13 m2 [140 sf]; Small
company 11.2 m2 [120 sf]. Provide access from Equipment Maintenance Area.
2-3.2.5.1 Function: Storage of equipment for use in defense of nuclear, biological or chemical
warfare.
2-3.2.5.2 Adjacency requirements: Adjacent to Equipment Maintenance Area.
2-3.2.5.3 Furnishings/Fixtures/Equipment: [add requirements for shelving].
Floor: sealed concrete
Base: resilient cove base
SOW-33