Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-3.3.2.4 Finishes: Floor: sealed concrete
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required
2-3.3.2.5 Other requirements: Electrical service to buildings shall be underground. Doors
shall have storeroom function (F86) locksets.
2-3.3.3
Interior Stairs. Provide as required to allow circulation to upper floor of the building,
and to comply with applicable code egress requirements. At least one stair connecting second
and first floors shall be an interior stair. [Revise if exterior stairs are not acceptable due to
regional climate.]
2-3.3.3.1 Function: Circulation and means of egress.
2-3.3.3.2 Adjacency requirements: Adjacent to corridors or breezeways. Connects all floors of
the building.
2-3.3.3.3 Furnishings/Fixtures/Equipment (FFE): Stairs shall be steel construction with
concrete-filled treads, or cast-in-place concrete construction. Open risers are prohibited.
Provide mechanical and electrical systems to comply with applicable codes.
2-3.3.3.4 Finishes:
Landing floor: porcelain tile, quarry tile, resilient tile, vinyl composition tile, or sealed concrete.
Base: porcelain tile, quarry tile, or resilient cove base.
Treads: porcelain tile, quarry tile, resilient treads, or sealed concrete. Provide slip-resistant nosing
if tile is used.
Risers: painted steel, porcelain tile, quarry tile, or sealed concrete.
Walls: painted impact resistant gypsum wallboard, or painted concrete masonry units.
Ceiling: suspended acoustical panel ceiling, painted gypsum wallboard, painted veneer plaster, or
painted Portland cement plaster.
2-3.3.3.5 Other requirements: Stairs shall comply with handicap accessibility requirements of
applicable codes. Railings shall be painted steel, or prefinished aluminum.
2-3.3.4
Exterior Stairs. Provide as required to allow circulation to upper floor of the building.
Comply with applicable code egress requirements. Exterior stairs shall be covered. [Delete this
paragraph if regional climate precludes the use of exterior stairs.]
2-3.3.4.1 Function: Circulation and means of egress.
2-3.3.4.2 Adjacency requirements: Adjacent to corridors or breezeways. Connects all floors of
the building.
2-3.3.4.3 Furnishings/Fixtures/Equipment (FFE): Exterior stairs shall be cast-in-place concrete
construction (preferred), or galvanized steel construction with concrete-filled treads. Open risers
and metal grating treads are prohibited.
2-3.3.4.4 Finishes: Landing floor: sealed concrete with slip-resistant finish texture.
Base: none required
Treads: Sealed concrete with slip-resistant nosing
SOW-36