Men's Locker Room. Provide one or more rooms, sized to accommodate the
number of lockers and plumbing fixtures required for each company served. Provide exterior
entrance(s) with airlock vestibule. Locker room may also be accessed from a common interior
public corridor in the COF building. For egress purposes, the occupant load shall be equal to
the higher of the following numbers: a) the number of lockers in the room, or b) the code
determined number of occupants calculated by multiplying room area x the occupant load
factor.
2-3.4.2.1 Function: Toilets, showers and lockers for male soldiers.
2-3.4.2.2 Adjacency requirements: Near Women's Locker Room. Near company operations
facilities.
2-3.4.2.3 Furnishings/Fixtures/Equipment (FFE): Provide floor mounted toilets, wall-hung
lavatories, and ceramic tile shower enclosures in the quantities indicated in the table above.
Provide toilet partitions at each toilet. Provide the following toilet accessories: one mirror with
shelf above each lavatory; one paper towel dispenser/waste receptacle per two lavatories (or
fraction thereof); one soap dispenser per lavatory; one toilet tissue dispenser per toilet; one
soap holder per shower; one shower curtain and rod at each shower; one double pin robe hook
outside each shower; one robe hook on each toilet partition door. Provide 305 mm [1'-0"] of
locker room bench per 5 lockers provided. Provide two wall mounted hand-held electric hair
dryers per each two lavatories (or fraction thereof); mount adjacent to mirrors. Provide fire
extinguishers in semi-recessed fire extinguisher cabinets to comply with applicable codes
Floor: porcelain tile, or ceramic tile.
Base: porcelain tile, or ceramic tile.
Walls: ceramic tile, or 1829 mm high ceramic tile wainscot with painted impact resistant gypsum
wallboard or painted concrete masonry units above.
Ceiling: painted Portland cement plaster, or suspended cement board with synthetic finish system.
2-3.4.2.5 Other requirements:
Janitor Closet. Provide one at each group of Locker Rooms. Minimum area: 6.5 m2
2-3.4.3
[70 sf]. Room shall be accessed from the exterior or from a common interior space (corridor or
vestibule); access directly from Men's or Women's Locker Room is not acceptable. If exterior
door to Janitor's Closet is provided, provide a covered sidewalk between Janitor's Closet and
locker rooms.
2-3.4.3.1 Function: Sink and storage of cleaning supplies, soap, paper products.
2-3.4.3.2 Adjacency requirements: Adjacent to Men's and Women's locker rooms.
2-3.4.3.3 Furnishings/Fixtures/Equipment (FFE): Provide one floor mounted mop sink, mop
rack for three mops, and minimum 3048 linear mm of wall mounted stainless steel shelving.
Floor: ceramic tile, or sealed concrete
Base: resilient cove base, or ceramic tile base
Walls: painted water-resistant gypsum wallboard, or painted concrete masonry units