Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
adjacent storage areas within the COF. Provide painted impact resistant gypsum wallboard, or
painted concrete masonry units at exterior walls and walls separating TA-50 Storage from
adjacent COFs.
Ceiling: painted exposed structure, or wire mesh.
2-3.2.7.5 Other requirements: Provide 914 mm [3'-0"] wide swinging door with keyed cylinder lock
in wire mesh partition at TA-50 Storage. Provide wire mesh ceiling or extend wire mesh partitions
to underside of structure above.
2-3.3
COF Support Areas. Provide the following areas in each COF building. Stairs shall be
provide in two-story structures. Only able-bodied personnel will occupy COF support areas;
handicapped accessibility is not required, except that stairs and corridors shall comply with
handicapped accessibility requirements of applicable codes.
2-3.3.1
Mechanical Room(s). Provide dedicated areas for mechanical equipment. Each
company shall have independent operation and control of HVAC system for its own spaces, but
mechanical equipment may serve more than one company, and mechanical rooms may be
combined. Mechanical rooms shall not be used for storage or other purposes. Access will be
limited to authorized personnel. Size and locate room(s) to allow equipment removal and
maintenance. Provide floor openings and vertical shaft spaces as necessary.
2-3.3.1.1 Function: Spaces for HVAC, water heating, and other plumbing and mechanical
equipment.
2-3.3.1.2 Adjacency requirements: Locate to allow efficient distribution. Mechanical rooms
located on the ground floor shall have doors opening to the exterior. Mechanical rooms on second
floor shall be accessed from corridors.
2-3.3.1.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
2-3.3.1.4 Finishes: Floor: sealed concrete
Base: resilient cove base, or none.
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required
2-3.3.1.5 Other requirements: Doors shall have storeroom function (F86) locksets.
2-3.3.2
Electrical Room(s). Provide dedicated areas for electrical equipment. Each company
shall have independent metering and control of the electrical system for its own spaces, but
electrical equipment may serve more than one company, and electrical rooms may be combined.
Electrical rooms shall not be used for storage or other purposes. Access will be limited to
authorized personnel. Size and locate room(s) to allow equipment removal and maintenance.
Provide floor openings and vertical shaft spaces as necessary.
2-3.3.2.1 Function: Spaces for electrical equipment.
2-3.3.2.2 Adjacency requirements: Locate to allow efficient distribution. Electrical rooms shall be
accessed from the exterior or from corridors.
2-3.3.2.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
SOW-35