Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
accessed from Administrative Area Corridor.
2-3.1.16.1 Function: Sink and storage of cleaning supplies, soap, and paper products.
2-3.1.16.2 Adjacency requirements: Adjacent to Administrative Area Corridor. Near Shower
rooms and toilets.
2-3.1.16.3 Furnishings/Fixtures/Equipment (FFE): Provide one floor mounted mop sink, mop
rack for three mops, and minimum 1524 linear mm of wall mounted stainless steel shelving.
Floor: ceramic tile, or sealed concrete
Base: ceramic tile base or resilient cove base
Walls: painted water-resistant gypsum wallboard, or painted concrete masonry units
Ceiling: painted gypsum wallboard, painted veneer plaster, or painted Portland cement plaster
2-3.1.16.5 Other requirements: Door shall have classroom function (F84) lockset.
2-3.1.17 Communication Room. Provide dedicated interior room(s) for communication
distribution equipment. Room(s) shall be dedicated to one company, and shall not be combined
with mechanical or electrical rooms. Room(s) may be accessed from Administrative Area Corridor,
public unsecure corridor (if provided), or Equipment Maintenance Area. Access will be limited to
authorized personnel. Provide each company with one main communication room; minimum size
3048 mm [10'-0"] x 3353 mm [11'-0"]. In two-story buildings, the communication room shall be
located on the second floor. Provide additional communication rooms as needed; all spaces having
telephone or computer data outlets shall be located to allow a maximum cable length of 90 m [295
feet] between outlet and communication room. Minimum dimensions of secondary communication
rooms shall be 2134 mm [7;-0"] x 3048 mm [10'-0"]. Provide floor openings and vertical shaft
spaces as necessary.
2-3.1.17.1 Function: Telephone and data network support spaces for the COF.
2-3.1.17.2 Adjacency requirements: Locate to allow efficient distribution. Communication rooms
shall not be used for storage or other purposes; access will be limited to authorized personnel.
2-3.1.17.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: painted gypsum wallboard, painted veneer plaster, or suspended acoustical panel ceiling
2-3.1.17.5 Other requirements: Door shall have minimum 914 mm [3'-0"] wide door with storeroom
function (F86) lockset.
2-3.3.1
Boot Wash Areas. Provide paved exterior boot wash area at each exterior entrance to
the COF Administrative Area. Design area for use by one soldier at a time.
2-3.3.1.1
Function: Exterior area for washing footgear prior to entering building.
2-3.3.1.2 Adjacency requirements: Locate on ground floor, adjacent to entrance.
SOW-30