Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-3.3.1.3 Furnishings/Fixtures/Equipment: Provide drainage assembly: Removable 914 mm x 914
mm aluminum or stainless steel grating, with non-slip surface, supported by concrete storm
drainage inlet box. Box shall be filled with stone and filter material to trap sediment . Filtered runoff
shall be piped to storm drainage system. Provide freeze-proof wall hydrant with aerator nozzle
mounted approximately 400 mm above grating, control valve mounted at 800 mm above pavement.
Provide 3'-0" long metal grab bar above control valve, mounted at 1067 mm above pavement. Top
of grating and concrete structure shall align with adjacent concrete sidewalk. Provide concrete
sidewalk between boot wash area and entrance sidewalk.
2-3.3.1.4 Finishes: refer to exterior building material requirements.
2-3.1.18
Other requirements: Provide adequate drainage away from building.
2-3.2
COF Supply Areas. Provide one group of supply areas per company; locate on the
ground floor. COF supply areas will be used to store, clean, and repair company operational
equipment and weapons. Individual TA-50 gear lockers shall be provided for approximately 30
percent of the company soldiers. Main entrance to supply areas will be from paved service
area; service area will be used for loading company equipment on and off of large trucks.
Entrance shall be separate and distinct from the entrances to company administrative areas and
to other COF supply areas. Exterior wall space above or adjacent to the entrance will be used
to display company identification signage. Provide interior circulation to company administrative
areas. Only able-bodied military personnel will occupy COF supply areas; handicapped
accessibility is not required. Wire mesh partitions shall be used to separate storage areas from
each other and from Equipment Maintenance Area. Provide the following areas for each
company:
2-3.2.1
Equipment Maintenance Area. Provide one area. Minimum area: Large company 123
m [1,325 sf]; Medium company 102.7 m2 [1,105 sf]; Small company 54.8 m2 [590 sf]. Main exterior
2
entry shall open to paved service yard. Provide interior access from COF administrative area via
administrative area corridor, stairs, or public unsecure corridor connecting other COFs in the
building.
2-3.2.1.1 Function: Equipment cleaning, repair and access to COF storage spaces.
2-3.2.1.2 Adjacency requirements: Adjacent to exterior paved area for loading equipment on large
vehicles. Adjacent to Arms Vault, TA-50 Lockers, and storage spaces. Adjacent to, or near
Administrative Area.
2-3.2.1.3 Furnishings/Fixtures/Equipment: Provide stainless steel equipment cleaning sinks 711
mm x 711 mm x 172 mm deep [28" x 28" x 6 "], (three sinks for large and medium companies, two
sinks for small companies), locate near exterior doors. Provide fire extinguishers in semi-recessed
fire extinguisher cabinets to comply with applicable codes. [Add requirements for shelving].
Floor: sealed concrete
Base: resilient cove base
Walls: painted impact resistant gypsum wallboard or painted concrete masonry units at exterior
walls and walls separating COFs. Painted concrete walls will separate Arms Storage from
Equipment Maintenance. Wire mesh partitions will separate storage areas from Equipment
Maintenance.
SOW-31