Project Name
Project Number
TEMF
Statement of Work
UFC 4-214-02, 24 Jul 03
2-2.2.12.2 Adjacency requirements: Adjacent to corridors, exterior entrances. Main stair should
be located close to main entrance of core
2-2.2.12.3 Furnishings/Fixtures/Equipment: Provide exit signage. Stair doors shall have glazed
panels (comply with code requirements for fire ratings and safety glazing). Exterior stairs shall
be cast-in-place concrete construction (preferred), or galvanized steel construction with
concrete-filled treads. Open risers and metal grating treads are prohibited.
2-2.2.12.4
Landing floor: sealed concrete with slip-resistant finish texture.
Base: none
Treads: Sealed concrete with slip-resistant finish texture. Provide slip-resistant nosing.
Risers: painted galvanized steel, or sealed concrete.
Walls at Interior Stairs: painted concrete, painted concrete masonry units, or painted gypsum
wallboard
Ceiling at Interior Stairs: painted exterior gypsum soffit board, or suspended acoustical panel
ceiling
Soffits at Exterior Stairs: painted exterior gypsum soffit board, painted Portland cement plaster,
or painted underside of concrete structure above.
2-2.2.12.5 Other requirements: [ ].
2-2.2.13 Mechanical Areas. Provide dedicated interior spaces and exterior areas for
plumbing, fire protection, and HVAC equipment. Size and locate rooms to allow equipment
removal and maintenance Provide floor openings and vertical shaft spaces as necessary.
2-2.2.13.1 Function: Mechanical support spaces for the building.
2-2.2.13.2 Adjacency requirements: Locate main mechanical room on ground floor with doors
opening to exterior. . Mechanical support spaces shall not be used for storage or other
purposes; access to mechanical spaces will be limited to authorized personnel. Locate exterior
mechanical equipment and air intake and openings in exterior walls to comply with force
protection standards.
2-2.2.13.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Floor: sealed concrete
Base: none
Walls: painted gypsum wallboard, or exposed concrete, or concrete masonry units
Ceiling: none
2-2.2.13.5 Other requirements: Locate air intake and exhaust openings to provide optimum
indoor air quality. Roof mounted equipment shall not be used. Provide masonry screen walls
[with lockable metal access gates] around outdoor equipment areas (refer to Chapter 3)
[Coordinate with requirements of Installation Design Guide] ; comply with force protection
standards.
2-2.2.14 Electrical Rooms. Provide dedicated interior spaces and exterior areas for
electrical equipment. Size and locate rooms to allow equipment removal and maintenance.
Provide floor openings and vertical shaft spaces as necessary. Provide minimum of one
electrical room per floor.
SOW-25