Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-2.4.6
Mechanical Areas. Provide dedicated interior spaces and exterior areas for plumbing,
fire protection, and HVAC equipment. Size and locate rooms to allow equipment removal and
maintenance Provide floor openings and vertical shaft spaces as necessary.
2-2.4.6.1 Function: Mechanical support spaces for the UEPH building.
2-2.4.6.2 Adjacency requirements: Locate main mechanical room on ground floor with doors
opening to exterior. Mechanical support spaces shall not be used for storage or other purposes;
access to mechanical spaces will be limited to authorized personnel. Locate exterior mechanical
equipment and air intake and openings in exterior walls to comply with force protection standards.
Do not locate mechanical equipment rooms adjacent to living units (shared walls).
2-2.4.6.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Floor: sealed concrete
Base: resilient cove base, or none
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required
2-2.4.6.5 Other requirements: Locate air intake and exhaust openings to provide optimum indoor
air quality. Roof mounted equipment shall not be used. Provide masonry screen walls with lockable
metal access gates around outdoor equipment areas (refer to Chapter 3); comply with force
protection standards. Doors shall have storeroom function (F86) locksets.
2-2.4.7
Electrical Rooms. Provide dedicated interior spaces and exterior areas for electrical
equipment. Size and locate rooms to allow equipment removal and maintenance. Provide floor
openings and vertical shaft spaces as necessary. Provide minimum of one electrical room per floor.
2-2.4.7.1 Function: Electrical support spaces for the UEPH building.
2-2.4.7.2 Adjacency requirements: Locate main electrical equipment room on ground floor.
Electrical rooms on upper floors should be located to allow efficient distribution. Size and locate
rooms to allow equipment removal and maintenance. Electrical rooms shall not be used for storage
or other purposes; access to electrical rooms will be limited to authorized personnel. Locate exterior
electrical equipment to comply with force protection standards.
2-2.4.7.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Floor: sealed concrete
Base: resilient cove base, or none.
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required
2-2.4.7.5 Other requirements: Electrical service to the building shall be underground. Provide
masonry screen walls with lockable metal access gates around outdoor equipment (refer to Chapter
3); it is preferable to locate transformer within the screened mechanical equipment area. Comply
with force protection standards. Door shall have storeroom function (F86) lockset.
2-2.4.8
Communication Rooms.
Provide dedicated interior rooms for communication
SOW-20