Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-2.4.10.1 Function: Storage for the following items (not in contract): lawn mowers, landscape
maintenance equipment, snow removal equipment, tools, and one flammable storage cabinet for
storing maximum of one five-gallon safety can of gasoline, and twelve one-quart containers of motor
oil.
2-2.4.10.2 Adjacency requirements: Locate remote from UEPH and other occupied buildings. It is
preferable to locate the storage building adjacent to the trash dumpster area. Comply with building
code setback requirements. Provide minimum force protection setback of 24.4 meters [80 feet] to
UEPH buildings and any other inhabited buildings.
2-2.4.10.3 Furnishings/Fixtures/Equipment: Provide one interior light fixture with safety cage,
controlled by occupancy sensor switch. No electrical receptacles shall be provided.
2-2.4.10.4 Building materials: Floor: sealed concrete slab on grade.
Exterior wall material: Masonry to match materials used on masonry screen walls.
Structure: Non-combustible materials. Fire-retardant wood or plywood shall not be used.
Roofing: match roof of UEPH building.
Interior wall finish: painted impact resistant gypsum wallboard or painted concrete masonry units.
Ceiling: painted exposed structure.
2-2.4.10.5 Other requirements: Provide wall louvers to allow natural cross-ventilation. Roof
penetrations are not acceptable. Provide hollow metal door and frame with storeroom function
(F86) lockset. Comply with NFPA 30 requirements for storage of flammable materials. Provide
minimum 1219 mm [4'-0"] wide sidewalk from entry door to adjacent pavement or sidewalk. Provide
bracket-mounted fire extinguisher.
2-3
COMPANY OPERATIONS FACILITIES FUNCTIONAL AND AREA
REQUIREMENTS. The company operations facilities (COF) building(s) shall consist of
administrative areas and supply areas for each company, support spaces, and common
locker/shower facilities. 11-16 personnel will staff each COF. Provide facilities for [ ] large
companies, [ ] medium companies, and [ ] small companies. Net areas of administrative
spaces are the same for each size company; net areas of supply spaces and locker/shower
facilities vary with company size. Total gross area of each size COF shall not exceed the
following: Large company 1094 m2 [11,776 sf]; medium company 857 m2 [9,227 sf]; small
company 722 m2 [7,770 sf]. Total gross building area of all COF buildings shall not exceed [
] m2 [_____ sf] [Maximum gross area shall be as shown on form DD 1391]. Facilities may
comprise a single building or multiple buildings. Buildings may be one or two stories in height.
In a two-story configuration, supply and locker/shower areas shall be located on the first floor;
administrative functions may be located on the second floor. An elevator is not required.
Grouping multiple COF's in one building is encouraged, however, each company must function
independently, and must be secured from other COFs. Provide separate exterior entrances to
the administrative and supply areas of each COF. Common mechanical rooms may be used,
but mechanical and electrical systems must provide each company with independent operation
and control. Locker/shower spaces may be combined and shared by all companies in a
building, or combined locker/shower spaces may be located in a separate building. To the
greatest extent possible, buildings shall be arranged to allow future reconfiguration of company
sizes (for example, changes in mission may require the conversion of a building housing two
large companies and one medium company into a building housing four small companies. In
this example, an addition would be constructed to house the administrative functions of the
fourth company, and supply areas originally designed for three companies could be
SOW-22